The Veris TFDCR00 RTD duct-mount temperature sensor is pre-calibrated and housed in sturdy stainless steel probes. This cost-effective device is easy-to-install, durable, highly accurate, and requires no calibration.
Product Specifications
| Wiring |
22AWG; 2-wire |
| Transmitter - Input Power |
Loop powered 12-30VDC only, 30mA max |
| Transmitter - Temp Output |
2-wire, loop powered 4-20mA |
| Transmitter - Sensor Type |
1k platinum, RTD, solid-state,
integrated circuit (Transmitter) |
| Transmitter - Accuracy |
±0.5°C (±1°F) typical |
| Transmitter - Ranges |
0° to 50°C (32° to 122°F), -40° to
50°C (-40° to 122°F) |
| Linitemp - Input Power |
5 to 30VDC |
| Linitemp - Output |
1µA/°C or 10mV/°C |
| Linitemp - Operating Temperature |
-25° to 105°C (-13° to 221°F) |
| Linitemp - Accuracy - Calibration
Error |
1.5°C (35°F) typical; 2.5°C (37°F)
max. at 25°C (77°F)* |
| Linitemp - Accuracy - Error over
Temperature |
1.8°C typical (35°F); 3.0°C (34°F)
max. over 0° to 70°C (32° to 158°F) range
2.0°C (35°F) typical, 3.5°C (38°F) max. over -25° to 105°C (-13° to 221°F) range |
| Enclosure |
Duct with Mounting Box |
| Probe Length |
8" |
| Output |
Resistive Out |
| Cal Certificate |
No |
| |
*Room temperature error documented on
each unit. |