The Veris Industries H708 current switch offers high performance, with a wide array of amperage range options. This product can accurately detect belt loss, coupling shear, or other mechanical failure on loads from 1/5 to 100HP. Now you can easily detect when drive belts slip, break, or pump couplings shear. In fact, a typical HVAC motor that loses its load has a reduction of current draw of up to 50%. That's why Veris sensors are the industry standard for status.
Features
The Veris H708 is used for detecting belt loss, coupling shear, and mechanical failure, verifying lighting circuit and other electrical service run times, monitoring status of industrial process equipment and critical motors (compressor,fuel, etc.)
The H708 is a high performance device in a solid-core housing. With a minimum trip point as low as 1.0A or less, this switch eliminates the need for multiple wraps of the conductor through the sensor even on loads as small as 1/5HP. The small size fits easily inside small enclosures and status LEDs for easy setup and local indication. One Amp status output for increased application flexibility. This device is 100% solid state and polarity insensitive, with a 5-year warranty.
Product Specifications
| Sensor |
Power Induced from monitored conductor |
| Insulation Class |
600VAC RMS (UL), 300VAC RMS (CE) |
| Frequency Range |
50/60 Hz |
| Temperature Range |
-15° to 60°C (5° to 140°F) |
| Humidity Range |
10-90% RH, non-condensing |
| Hysteresis |
10% (typical) |
| Terminal Block Maximum Wire Size |
14 AWG |
| Terminal Block Torque (nominal) |
4 in-lbs |
| Amperage Range |
1 - 135A |
| Status Output |
N.O.1.0A@30VAC/DC |
| Min Trip Point |
1.0A or less |
| Housing |
Solid cone |
| Status LED |
Yes |
| Agency Approvals UL |
508 open device listing |
| CE: |
EN61010-1:2001-02, CAT III, deg. 2,
basic insulation |
| Comments |
Do not use the LED status indicators
as evidence of applied voltage.
For applications requiring double or reinforced insulation, please contact the
factory. |