The TAC-Invensys MP-5413 Hydraulic Actuator provides electronic proportional control of dampers, valves, or program switches requiring the return to normal position upon power interruption.
Features
The MP-5413 offers proportional control by variable Vdc input signal and is compatible with 2 to 15 Vdc System 8000 input signals. Includes spring return, fixed 3 Vdc operating span, adjustable 2 to 12 Vdc start point for paralleling or sequencing of actuators, 10,000 O or greater input impedance. Damper models with linkage or base models that require separate damper or valve linkage. Durable die cast lower housing with 1/2 in. conduit opening and painted steel upper housing. The hydraulic actuator comes with oil immersed motor, transducer,and pump.
Product Specifications
| Actuator Power Input |
|
AC Voltage
+10/-15% |
24 |
50/60 Hz
Watts
Amps
|
18
10 |
| Positive Positioner1 |
Yes |
| Timing in Seconds at 72°F (22°C) |
|
No Load Stroke
To Extend
To Retract
Retract on Power Loss
|
60
30
15 |
| Required Linkage |
|
| Damper Valve |
AM-6012 AV-600 or
AV-7600-1
AV-6013 |
1 Internal
feedback circuitry provides positive positioning of valve stem in relation to
control signal.
2 With the installation of the AM-601 damper linkage, these valve
actuators become functionally the same as the damper actuators listed under
Damper Actuators.
3 May be required for steam and hot water. Refer to Maximum Allowable
Ambient Temperature for the Valve Actuator. |
Maximum Allowable Ambient Air Temperature for Valve Actuators.
| Temperature of Media in the Valve Body
(Check the Rating of the Valve) °F (°C) |
Maximum Allowable Ambient Air Temperature |
| AV-600 or AV-7600-1 Only for Chilled
Water Applications °F (°C) |
AV-600 or AV-7600-1 with AV-601
Extension °F (°C) |
| 366 (180) |
Do Not Use |
88 (31) |
| 340 (171) |
93 (34) |
| 281 (138) |
103 (39) |
| 181 (83) |
120 (48) |
| 80 (26) |
140 (60)* |
140 (60) * |
| *Maximum allowable ambient temperature of
the actuator. |
| Inputs |
Compatible with 2 to 15 Vdc from
System 8000 controllers |
| Operating span |
Approximately 3 Vdc fixed |
| Start point |
Adjustable 2 to 12 Vdc. Factory set at
6 Vdc. Impedance 10,000 O or greater |
| Connections |
Color-coded 4 ft (1.2 m) leads. |
| Electrical Internal Power Supply |
20 Vdc, 25 mA. |
| Stroke, Damper |
Approximately 2 in. (51 mm) over a
nominal 6 Vdc (fully retracted) to 9 Vdc (fully extended) input range (includes
AM-601 linkage). |
| Stroke, Valve |
Approximately 9/16 in. (14 mm) over a
nominal 6 Vdc (fully retracted) to 9 Vdc (fully
extended) input range |
| Nominal Damper Area |
Actuator sizing should be done in
accordance with damper manufacturer’s specifications. |
| Ambient temperature limits |
|
| Operating |
-20 to 140°F (-29 to 60°C). |
| Damper |
-20 to 140°F (-29 to 60°C). |
| Valve |
Refer to Maximum Allowable Ambient Air
Temperature for Valve Actuators. |
| Humidity |
5 to 95% RH, non-condensing |
| Location |
NEMA Type 1 |
| Dimensions |
6-3/4 H x 3-23/32 W x 3-1/4 D in. (171
x 18 x 83 mm) |
| Agency Listings |
UL UL873 File E9429 Temperature
Indicating and Regulating Equipment, CUL Canadian Standard (File #LR3728).
European Community EMC Directive 89/336/EEC, Low Voltage Directive 72/23/EEC. |