Johnson Controls VA-7452-90011 - Electric Valve Actuator

 
$98.60
SKU:
VA-7452-90011
Qty:
 
 

The Johnson Controls VA-7452-90011 electric valve actuator provides proportional control HVAC applications. The compact design of this actuator makes it ideal for installations in confined locations, such as fan coil applications. The Johnson Controls VA-7452-90011 is designed for easy mounting in the field, or may be ordered factory coupled to Johnson Controls® VG4000 or VG5000 Series Zone Valves. Refer to the VA-7450 Series Electric Valve Actuators Product Bulletin (LIT-977324) for important product application information.

Features

The Johnson Controls VA-7452-90011 includes auto-commissioning, which simplifies installation, since the actuators require no adjustments in the field. The auto-shutoff actuator motor extends actuator life by reducing drive time and excessive motor wear, while the durable, heat-stabilized, plastic resin enclosure allows the actuator to be used in applications with fluid temperatures up to 203°F (95°C). The VA-7452-90011 can be mounted after the valve body is piped, simplifying installation and providing application flexibility. This actuator may even  be rotated after it is mounted on the valve body, simplifying installation by allowing the actuator wiring entry to be located in any direction. LED provides direct, visual indication of the actuator operating status.

Product Specifications

Power Requirements 24 VAC ±15% at 50/60 Hz; 5.0 VA at Maximum Power Supply; Class 2
Input Signal 0 to 10 VDC
Input Signal Adjustments Input Signal: 0 to 10 VDC, 0 to 5 VDC, or 5 to 10 VDC
Direction: Direct (Drive Down) or Reverse (Drive Up) with Input Signal Increase
Valve Type: Two-Way N.O. (PDTC), Two-Way N.C. (PDTO), or Three-Way Mixing
Factory Settings: 0 to 10 VDC, Direct (Drive Down), and Two-Way N.O. (PDTC)
Input Impedance 80,000 ohms
Electrical Connections 24 AWG Cable; 20 in. (508 mm) Long
Mechanical Connections Threaded Coupling for Johnson Controls VG4000 or VG5000 Series Zone Valves
Enclosure Glass and Mineral-Filled Kelon A Plastic Resin; NEMA 1, IP40 (EN 60529)
Output Force 21.5 lb (96 N) Minimum
Stroke 0.20 in. (5 mm) Maximum
Full Stroke Cycle Time 65 Seconds
Full Stroke Cycles 100,000
Audible Noise Rating 25 dBA Maximum at 3.3 ft (1 m)
Fluid Temperature Limits 35 to 203°F (2 to 95°C)
Ambient Operating Conditions 32 to 122°F (0 to 50°C), Noncondensing
Ambient Storage Conditions -4 to 149°F (-20 to 65°C), Noncondensing
Agency Compliance UL 873 Listed, File E27734, CCN XAPX, Suitable for Plenum Use;
CSA C22.2 No. 139 Certified, File LR85083, Class 3221 01
CE Conformity EMC Directive (89/336 EEC)