The Honeywell Y8610U6006 is a Y-pack containing S8610U3009 and VR8304M with 1/2 inch by 3/4 inch inlet/outlet, flange kit, and LP conversion kit. For use with 24 Vac gas-fired atmospheric furnaces, boiler and heating appliances.
Features
The Y8610U6006 kits are for use with natural or LP gas: provides 100 percent pilot gas shutoff if pilot fails to light; after 6-minute delay, trial for ignition is repeated. The ignition trail/delay sequence is repeated until the appliance lights or call for heat is removed.
Product Specifications
| Description | Provide electronic control of intermittent pilot ignition systems used on gas fired furnaces, boilers, and other heating appliances. |
| Ignition System Type | Intermittent Pilot |
| Ignition Sequence | Continuous retry, after trial for ignition, pilot gas shuts off for 5 minutes, then another trial for pilot ignition takes place |
| Typical Gas Control | VR8204, VR8304 |
| Type of Gas | Natural or LP |
| Flame Sense | Single Rod or Two Rods |
| Ignition Source | Internal high voltage spark generator |
| PrePurge | 0 or 30 seconds |
| Ignition Trials To Lockout | continuous retry |
| Lockout Timing | 15 or 90 seconds |
| Ignition Trial Time (sec) | 15 or 90 seconds |
| Maximum Valve Load @ 24 Vac (Amps) | 1A Pilot, 2A Main @ 24Vac |
| Typical Ignition Hardware | Q345, Q3451 |
| Dimensions (in.) | 3-15/16 in. high x 5-7/16 in. wide x 2-5/8 in. deep |
| Dimensions (mm) | 100 mm high x 138 mm wide x 67 mm deep |
| Electrical Ratings | 24 Vac |
| Frequency | 60 Hz |
| Maximum Ambient Temperature (F) | -40 F to +165 F |
| Maximum Ambient Temperature (C) | -40 C to +74 C |
| Includes | VR8304M3558 (1/2 x 3/4; 3.5" setting; 270kBtu/hr at 1 in. p.d.) |
| Flame Failure Response Time (sec) | 2.0 sec |