Honeywell Y8610U6006 - Y-Pack

 
$238.45
SKU:
Y8610U6006
Qty:
 
 

The Honeywell Y8610U6006 is a Y-pack containing S8610U3009 and VR8304M with 1/2 inch by 3/4 inch inlet/outlet, flange kit, and LP conversion kit. For use with 24 Vac gas-fired atmospheric  furnaces, boiler and heating appliances.

 

Features 
 
The Y8610U6006 kits are for use with natural or LP gas: provides 100 percent pilot gas shutoff if pilot fails to light; after 6-minute delay, trial for ignition is repeated. The ignition trail/delay sequence is repeated until the appliance lights or call for heat is removed.

 

Product Specifications

 

DescriptionProvide electronic control of intermittent pilot ignition systems used on gas fired furnaces, boilers, and other 
heating appliances.
Ignition System TypeIntermittent Pilot
Ignition SequenceContinuous retry, after trial for ignition, pilot gas shuts off for 5 minutes, then another trial for pilot ignition takes place
Typical Gas ControlVR8204, VR8304
Type of GasNatural or LP
Flame SenseSingle Rod or Two Rods
Ignition SourceInternal high voltage spark generator
PrePurge0 or 30 seconds
Ignition Trials To Lockoutcontinuous retry
Lockout Timing15 or 90 seconds
Ignition Trial Time (sec)15 or 90 seconds
Maximum Valve Load @ 24 Vac (Amps)1A Pilot, 2A Main @ 24Vac
Typical Ignition HardwareQ345, Q3451
Dimensions (in.)3-15/16 in. high x 5-7/16 in. wide x 2-5/8 in. deep
Dimensions (mm)100 mm high x 138 mm wide x 67 mm deep
Electrical Ratings24 Vac
Frequency60 Hz
Maximum Ambient Temperature (F)-40 F to +165 F
Maximum Ambient Temperature (C)-40 C to +74 C
IncludesVR8304M3558 (1/2 x 3/4; 3.5" setting; 270kBtu/hr at 1 in. p.d.)
Flame Failure Response Time (sec)2.0 sec