• Microprocessor-based integrated flame switch
• Used to detect flame using rectification, ultraviolet (UV) or infrared (IR) source
• Provides safety level, functional capability & features beyond conventional controls.
• Fits any 7800 Series Amplifier to provide relay action from two single pole, double throw (SPDT) relays when flame is present or not present. RM7823A and EC7823 are a flame detector relays only.
• Suitable primary control must be used to provide safe-start check, safety lockout, load switching and other functions required in flame safeguard systems.
• Three LEDs to indicate power, flame and alarm.
• Access for external electrical voltage checks.
• Nonvolatile memory.
• Shutter drive output.
• Compatible with existing Honeywell flame detectors.
| Required Components | Q7800A,B Universal Wiring Subbases. R7847, R7848, R7849, R7851, R7852, R7861, or R7886 Flame Signal Amplifier. |
| Voltage | 120 Vac (+10, -15%) |
| Vibration | 0.5 G environment |
| Ambient Temperature Range (F) | -40 F to +140 F |
| Ambient Temperature Range (C) | -40 C to +60 C |
| Dimensions (in.) | 5 in. wide x 5 in. high x 5 1/4 in. deep with Q7800A Subbase x 6 3/32 in. deep with Q7800B Subbase |
| Dimensions (mm) | 127 mm wide x 127 mm high x 133 mm deep with Q7800A Subbase x 155 mm deep with Q7800B Subbase |
| Approvals, Underwriters Laboratories Inc | Component Recognized, File No. MP268; Guide No. MCCZ. |
| Approvals, Canadian Standards Association | Certified, File No. LR95329-3. |
| Approvals, Federal Communications Commission | FCC Part 15, Class B, Emissions. |
| Approvals, Swiss RE (formerly IRI) | Acceptable |
| Approvals, Factory Mutual | Report No. OX4A5.AF. |
| Comments | two SPDT outputs |