| Description |
Switching relay with internal
transformer, provides Dpst switching for hot water zone control systems, or spst
control of two separate loads. |
| Application |
Provide intermediate switching of a
line voltage device form a low voltage controller. |
| Switching Action |
DPST; one pole line voltage, the other
line or low voltage |
| Coil Ratings Current |
0.4A |
| Coil Ratings Voltage |
24 Vac |
| Transformer Primary Rating |
120 Vac, 50/60 Hz |
| Transformer Secondary Rating |
24 Vac |
| Temperature Range (F) |
115 F maximum ambient for 60 Hz. 105 F
Max. Ambient for 50 Hz. |
| Temperature Range (C) |
46 C maximum ambient for 60 Hz. 41 C
maximum ambient for 50 Hz. |
| Thermostat Compatibility |
Low voltage (Class 2) 2-wire |
| Dimensions (in.) |
5 1/4 in. high x 4 1/4 in. wide x 2
5/16 in. deep |
| Dimensions (mm) |
133 mm high x 108 mm wide x 59 mm deep |
| Electrical Connections(Control
Circuit) |
2-Wire |
| Electrical Ratings (Maximum Input) |
5.0 W |
| Electrical Ratings (Primary
Voltage) |
120V, 50/60 Hz |
| Contacts Electrical Rating Main
Contacts 120 Vac |
7.4A AFL; 44.4A ALR; 10A Resistive |
| Contacts Electrical Rating
Secondary Contacts 120 Vac |
3A ALF; 18A ALR |
| Contacts Electrical Rating Main
Contacts 240 Vac |
3.7A ALF; 22.2A ALR; 6.0A Resistive |
| Contacts Electrical Rating
Secondary Contacts 240 Vac |
2A AFL; 12A ALR |
| Contacts Electrical Rating
Secondary Contacts Pilot Duty |
Rat 50 VA @ 24V |
| Contacts Electrical Rating Contacts
Max. Connected Load |
2000 VA (120 Vac to 240 Vac) |
| Includes |
Integral transformer, enclosure |
| Approvals, Underwriters
Laboratories Inc |
Listed: File No. E4436, Guide No. XAPX |
| Approvals, Canadian Standards
Association |
Certified: File No. LR1620 |
| Tradeline Value |
Tradeline |