The Honeywell R8184G4009 Protectorelay Oil Burner Control with 45 seconds lock-out timing. Provides automatic, nonrecycling control of an intermittent ignition oil burner system.
Features
The R8184G4009 controls oil burner, oil valve (if desired) and the ignition transformer in response to a call for heat. Includes solid state flame sensing circuit, LED on terminal strip to indicate system lockout, enclosed safety switch with external reset button and a manual trip lever which opens safety switch for system maintenance. Remote lockout indication available on some models. Mounts on standard 4 x 4 in. junction box; select models may be mounted directly on burner housing. C554A Cadmium Sulfide Flame Detector and 24 Vac thermostat required.
Product Specifications
| Description |
Protectorelay® Oil Burner Control with
45 seconds lock out timing |
| Ignition Type |
Intermittent |
| Timing, Safety Switch |
45 sec |
| Mounting |
Bracket For mounting on a standard 4
in. X 4 in. junction box or direct mounting on burner housing |
| Electrical Rating; Contacts (full
load) |
7.4 A @ 120 Vac; 3.7 a @ 240 Vac |
| Electrical Rating; Contacts (locked
rotor) |
44.4 A @ 120 Vac; 22.2 A @ 240 Vac |
| Alarm Load Ratings (pilot duty) |
75 VA @ 120/240 Vac, 50-60 Hz; 25 VA @
24V, 50-60 Hz |
| Alarm Load Ratings (resistive) |
1.5 A @ 120/240V, 50-60Hz; 3 A @ 24 V,
50-60 Hz |
| Dimensions (in.) |
4 3/8 in. high x 4 1/8 in. wide x 2
1/2 in. deep |
| Dimensions (mm) |
111 mm high x 104 mm wide x 64 mm deep |
| Temperature Range (F) |
-40 F to +130 F |
| Temperature Range (C) |
-40 C to +54 C |
| Approvals, Underwriters
Laboratories Inc |
UL Component Recognized; File no.
MP268, Vol. 35 Sec. 1,3 |
| Approvals, Canadian Standards
Association |
CSA Certified; File no. LR95329-1 |
| Comments |
With LED for lockout indication, and
manual trip lever on safety switch to assure burner shutdown during servicing. |
| Tradeline Value |
Tradeline |