The compact Honeywell C7027A1049 is designed for use with flame safeguard controls with ultraviolet amplifiers.
Features
The C7027A1049 is designed mainly for Use with Honeywell Flame Safeguard primary safety controls and burners requiring ultraviolet flame detection. The sensor mounts on a 1/2-inch sighting pipe utilizing an integral collar, and the compact size allows for blast tube mounting. These detectors can be wired in parallel for difficult sighting applications while sealing against pressures up to 5 psi (34.5kPa) when correctly installed.
Product Specifications
| Type |
Ultraviolet, Minipeeper |
| Application |
Coal-fired, Gas-fired, and Oil-fired
burners |
| Lead Length (in.) |
96 in. |
| Lead Length (mm) |
2438 mm |
| Electrical Connections |
2 NEC Class 1 leadwires |
| Ambient Temperature Range (F) |
0 F to 215 F |
| Ambient Temperature Range (C) |
-18 C to 102 C |
| Vibration |
0.5 G max |
| Mounting |
Integral nut for 1/2 in. sighting pipe |
| Dimensions (in.) |
1 1/16 in. diameter x 4 in. long |
| Dimensions (mm) |
27 mm diameter x 102 mm long |
| Approvals, Underwriters
Laboratories Inc |
Listed: File No. MP268, Guide No. MCCZ |
| Approvals, Canadian Standards
Association |
Certified: Master Report LR95329-1 |
| Approvals, Swiss RE (formerly IRI) |
Acceptable |
| Approvals, Factory Mutual Approved |
Report No. 24181.03 |
| Includes |
1/2 in. NPT threaded spud connector |
| Comments |
Detects ultraviolet radiation in
flames |
| Used With Flame Amplifiers |
R7249A, B, R7849A, B, R7749B, R7259,
R7290 |