Products > Flow Control Switches, Sensors > Honeywell C6097A1012 - Pressure Switch


Honeywell C6097A1012 - Pressure Switch

 
$79.10
SKU:
C6097A1012
Qty:
 
 

The Honeywell C6097A1012 pressure switch, with manual Reset, max. 2.4 in. wc at min setpoint and max 4.2 in. wc at max setpoint, is a safety device used in positive-pressure or differential-pressure systems to sense gas or air pressure systems.

Features 
 
The Honeywell C6097A1012 is for use with natural gas, liquid propane (LP) gas, or air and includes a diaphragm-actuated safety-limit switch which can be wired to turn on alarm. The C6097A1012 breaks control circuit at setpoint on pressure fall, and has a lockout with manual reset, recycle options, and an external manual reset button. A removable transparent cover protects scaleplate and adjusting knob while pipe tappings allow selection of positive pressure (air only) or venting connections (NPT mount only).Optional switch position indicator lamp available. IP54 enclosure standard.

Product Specifications

Description Pressure Switch, Manual Rest, max. 2.4 in. wc @ min. setpoint; max. 4.2 in. wc @ max. setpoint
Application Safety devices used in positive-pressure or differential-pressure systems to sense gas or air pressure changes
Operating Range (psi) 3 to 21 in. wc
Operating Range (kPa) 0.7 to 5.2 kPa
Mounting 1/4 in. NPT internal thread
Switch Operation Manual Reset
Switching Action Break on pressure fall
Pipe Connections Vent or Low pressure 1/8 in. NPT internal thread
Dimensions (in.) 3 17/32 in. high x 2 23/32 in. wide x 2 23/32 in. deep
Dimensions (mm) 90 mm high x 69 mm wide x 69 mm deep
Alternate Ratings Ignition Transformer: 540 VA, Pilot Valve: 50 VA.
Main Valve: 400 VA with 2-1/2 times inrush
Switch Contact Ratings (120 Vac) 3.0 AFL, 18.0 ALR, 5.0 A resistive
Switch Contact Ratings (240 Vac) 3.0 AFL, 18.0 ALR, 5.0 A resistive
Pressure Differential (psi) max. 2.4 in. wc @ min. setpoint;
max. 4.2 in. wc @ max. setpoint
Pressure Differential (kPa)  max. 0.60 kPa @ min. setpoint;
max. 1.05 kPa @ max. setpoint
Differential Type Additive
Temperature Range (F) -40 F to +140 F
Temperature Range (C) -40 C to +60 C
Electrical Connections Screw terminals
Approvals, Underwriters Laboratories Inc Component Listed
Approvals, Canadian Standards Association Certified
Approvals, Factory Mutual Approved
Approvals, Industrial Risk Insurers Acceptable
Approvals, Others CSD-1 AFB: Acceptable