The Honeywell C6097A1004 Pressure Switch ia a safety devices made for use in positive-pressure or differential-pressure systems, designed to sense gas or air pressure systems.
• For use with natural gas, liquid propane (LP) gas, or air.
• Diaphragm-actuated safety-limit switch.
• Switch can be wired to turn on alarm.
• C6097A models break control circuit at setpoint on pressure fall.
• Lockout with manual reset and recycle options.
• Lockout models have external manual reset button.
• Removable transparent cover protects scaleplate and adjusting knob.
• Pipe tappings allow selection of positive pressure (air only) or venting connections (NPT mount only).
• 1/4 in. NPT or flange mount models for direct mounting to Honeywell Integrated Valve Train.
• Optional switch position indicator lamp available.
• IP54 enclosure standard.
• Ranges: 0.4 to 5 in.wc, 3 to 21 in.wc, 12 to 60 in.wc or 1.5 to 7 psi.
• Surge orifice.
• Integral vent limiter on all models.
| Description | Pressure Switch, Auto recycle, Break N.O. to C. on pressure fall |
| Application | Safety devices used in positive-pressure or differential-pressure systems to sense gas or air pressure changes |
| Operating Range (psi) | 0.4 to 5 in. wc |
| Operating Range (kPa) | 0.10 to 1.25 kPa |
| Mounting | 1/4 in. NPT internal thread |
| Switch Operation | Auto recycle |
| Switching Action | Break on pressure fall |
| Pipe Connections, Vent or Low pressure | 1/8 in. NPT internal thread |
| Dimensions (in.) | 3 3/16 in. high x 2 23/32 in. wide x 2 23/32 in. deep |
| Dimensions (mm) | 81 mm high x 69 mm wide x 69 mm deep |
| Alternate Ratings | Ignition Transformer: 540 VA, Pilot Valve: 50 VA. Main Valve: 400 VA with 2-1/2 times inrush |
| Switch Contact Ratings (120 Vac) | 3.0 AFL, 18.0 ALR, 5.0 A resistive |
| Switch Contact Ratings (240 Vac) | 3.0 AFL, 18.0 ALR, 5.0 A resistive |
| Differential Type | Additive |
| Temperature Range (F) | -40 F to +140 F |
| Temperature Range (C) | -40 C to +60 C |
| Electrical Connections | Screw terminals |
| Nominal Pressure Differential (psi) | 0.16 in. wc |
| Nominal Pressure Differential (kPa) | 0.04 kPa |
| Maximum Pressure Differential (psi) | 0.24 in. wc |
| Maximum Pressure Differential (kPa) | 0.06 kPa |
| Approvals, Underwriters Laboratories Inc | Component Listed, MP 2168-8-1 |
| Approvals, Canadian Standards Association | File # 95329 Certificate 2632-01 |
| Approvals, Factory Mutual | JI 2D4A1.AF |
| Approvals, Swiss RE (formerly IRI) | Acceptable |
| Approvals, Others | CSD-1 AFB: Acceptable |